Electricity meter LoRaWAN DIN, three-phase indirect
A three-phase meter that measures through current transformers with a 1 A or 5 A secondary, for services where the currents are too high for direct measurement. MID- and ETL-approved.
Technical specifications
Function
Indirect three-phase meter via current transformer
Supply types
- 1p2w
- 1p3w
- 3p3w
- 3p4w
Measures
- kWh
- kVArh
- kW
- kVAr
- kVA
- power factor
- frequency
- voltage
- current
- demand
- THD
Current transformer
- Primary 1–9,999 A
- secondary 1 A or 5 A
Voltage
- Un 230 V L-N
- measuring range 173–480 V AC L-L / 100–276 V AC L-N
Auxiliary power supply
- 85–275 V AC / 120–380 V DC
- < 7 VA (3.5 W)
Accuracy
- Active energy Class 1 (IEC 62053-21)
- Reactive energy Class 2 (IEC 62053-23)
- Voltage and current ±0.5 %
Update rate
1 second
Communication
- LoRaWAN 1.0.2
- EU868
- Class C
- OTAA or ABP
- 13 dBm
Range
1,500 m in an open area
Ingress protection
IP51 (indoor)
Dimensions (W × H × D)
72 × 94.5 × 65 mm
Weight
330 g
Operating temperature
−40 °C to +70 °C
Humidity
99 % RH, non-condensing
Measurement category
CAT III (IEC 61010-1)
Certification
- MID 2014/32/EU
- ETL
Features
Built for large services
Current is measured through current transformers with a primary of 1 to 9,999 A, so the meter still fits where direct measurement will not.
MID- and ETL-approved
MID-approved by SGS and ETL-approved by Intertek, which is required for metering that underpins billing.
The whole power-quality picture
Beyond energy it logs voltage, current, power factor, frequency and THD, with one update per second.
LoRaWAN Class C
The unit listens continuously and reaches 1,500 metres in an open area, so settings can be changed remotely.