Electricity meter LoRaWAN DIN, three-phase direct

A three-phase DIN-rail meter with 100 A direct connection, a built-in relay and LoRaWAN. It measures active and reactive energy in both directions.

Technical specifications

Function
Three-phase direct meter, 100 A direct connection
Measures
  • kWh
  • kVArh
  • kW
  • kVAr
  • kVA
  • power factor
  • frequency
  • voltage
  • current
  • demand
Measurement direction
Import and export
Input voltage
  • 230 V AC
  • ±20 %
Current
  • Ib 5 A
  • Imax 100 A
Frequency
  • 50/60 Hz
  • range 45–65 Hz
Accuracy
  • Active energy Class 0.5 (IEC 62053-22)
  • Class C (EN 50470-1/3)
  • Reactive energy Class 2 (IEC 62053-23)
Pulse output
1,000 imp/kWh, fixed to active kWh
Display
  • LCD with white backlight
  • max 999,999.99 kWh
Relay
Built in, controlled over LoRaWAN, per phase or together
Interfaces
  • LoRaWAN
  • pulse output
  • 2 digital inputs
Power consumption
≤ 2 W
Mounting
35 mm DIN rail
Operating temperature
−40 °C to +70 °C
Humidity
0–100 %, non-condensing

Features

100 A without current transformers

A direct connection up to 100 A makes the installation simpler and cheaper than a solution with external current transformers.

Relay in the meter

The built-in relay switches over LoRaWAN, per phase or for all three at once, and trips at the alarm levels you set.

Measures both ways

Both consumed and exported energy are registered, which you need once the property has solar of its own.

A place in the distribution board

The meter mounts on a 35 mm DIN rail and sits alongside the other devices in the board.

Want to know more about Electricity meter LoRaWAN DIN, three-phase direct?

Get in touch and we will help you choose the right metering and connectivity for your property.

By submitting, we'll link this email to your previous visits to our site, ad clicks, and any marketing emails we send you, to make our follow-up relevant. Details and opt-out in our Privacy Policy.

Free and without obligation. Reply within 24 hours.